Eden Campus - Dry Room Facility for ACMF Project
University of St Andrews · Awarded
- Buyer
- University of St Andrews
- Status
- Awarded
- Country
- United Kingdom
- Region
- England
- Sector
- Manufacturing
- Reference
- FaT-ocds-h6vhtk-028e23
- Published
- 2021-01-28
Tender summary
We require a dry room, capable of housing lithium- and sodium-ion battery production. The dry room will sit within a modular building. Required components: - Dry space with dimensions of at least 8 m x 12 m and 2.65 m height - Airlock with floor space of least 2 m x 2 m, this can be within the dry space footprint or adjoining and include a ‘traffic-light’ system to control entry to the dry space - A maximum dew point of -40°C, preferably -50oC - External equipment access door with dimensions of 2 m x 2 m - Number of People = 3 - Lighting level 600lux @ 1m